Permit Number: T08CM02269
Parcel: 10511061E

Address:
160 W WETMORE RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM02269
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the detail showing the instant electric water heater (IWH-1) to include a shutoff valve prior to the expansion tank and the water heater (the thermal expansion tank shall not be isolated from the water heater with a valve). Reference: Sections 605.5 and 608.3, UPC 2006.
2. Terminating the excess pressure relief from the water heater over the floor drain as currently shown cannot be approved. The floor drain located in front of the service sink and unless it is equipped with a funnel top, it would not prevent splashing or flooding. Reference: Sections 608.5 and 804.1, UPC 2006.
01/19/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/27/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
01/27/2010 SUE REEVES REJECT SHELF Completed