Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM02269
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/19/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the detail showing the instant electric water heater (IWH-1) to include a shutoff valve prior to the expansion tank and the water heater (the thermal expansion tank shall not be isolated from the water heater with a valve). Reference: Sections 605.5 and 608.3, UPC 2006. 2. Terminating the excess pressure relief from the water heater over the floor drain as currently shown cannot be approved. The floor drain located in front of the service sink and unless it is equipped with a funnel top, it would not prevent splashing or flooding. Reference: Sections 608.5 and 804.1, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/27/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
01/27/2010 | SUE REEVES | REJECT SHELF | Completed |