Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM02269
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The detail showing how the instant electric water heater (IWH-1) is to be installed shows the thermal expansion tank being separated from the water heater by two valves. Revise the design so that the thermal expansion tank cannot be isolated from the water heater. Reference: Section 608.3, UPC 2006. 2. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Revise the routing of the T&P relief piping so that no portion of the pipe is trapped. Reference: Section 608.5, UPC 2006. |
| 01/07/2010 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/07/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The submitted ventilation calculations include a factor to reduce the floor areas to 2/3 of the net floor area. The occupant loads shown in Table 403.3, IMC 2006 are based on the net floor area and no area reduction is included in the 2006 IMC. Revise the calculations accordingly. Reference: Section 403.3, IMC 2006. |
| 12/23/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/14/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |