Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM02269
Parcel: 10511061E

Address:
160 W WETMORE RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM02269
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
01/07/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted ventilation calculations include a factor to reduce the floor areas to 2/3 of the net floor area. The occupant loads shown in Table 403.3, IMC 2006 are based on the net floor area and no area reduction is included in the 2006 IMC. Revise the calculations accordingly. Reference: Section 403.3, IMC 2006.
01/07/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The detail showing how the instant electric water heater (IWH-1) is to be installed shows the thermal expansion tank being separated from the water heater by two valves. Revise the design so that the thermal expansion tank cannot be isolated from the water heater. Reference: Section 608.3, UPC 2006.
2. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Revise the routing of the T&P relief piping so that no portion of the pipe is trapped. Reference: Section 608.5, UPC 2006.
12/23/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2010 DELMA ROBEY OUT TO CUSTOMER Completed