Permit Number: T08CM02255
Parcel: 11811011H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02255
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please clarify the location of the service equipment. On the line diagram Page 3, the label "Main Switchgear", the presence of the Grounding Electrode Conductor, and the note "From TEP" describe a system where the actual Service Disconnecting Means is in the enclosure "Main Switchgear". According to the layout on Page A 4, the switchgear is on the other side of the wall from the Service Main.
2. If the Electrical Service Disconnecting Means is on the building exterior, that is, not within the Main Switchgear inside, the Grounding Electrode Conductor would articulate there, not inside. See NEC Article 250.
3. If the Electrical Service Disconnecting Means is on the building exterior, please provide for the placards required by NEC 690.56 (B). Provide the exact wording.
4. Demonstrate compliance with NEC 690.64 (B) (2) at the Main Switchgear. Reference Page 3. This is not possible to evaluate without seeing the rating of the overcurrent protection for the Main Switchgear.
5. Specify the conduit which runs from the J-box to the Inverter. Since this runs inside of the building before encountering its Disconnecting Means, it must comply with the Exception to 690.14 (C). conduit shall be metallic per 690.31 (E).