Permit Number: T08CM02249
Parcel: 12701002C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02249
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2008 STEVE SHIELDS ZONING REVIEW Approved
06/25/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/25/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02249 6/25/08

1. Please coordinate with Mechanical and provide power for new VAV B-15 and VAV B-7.
2. VAV B-7 does not have electrical requirements. Sheet M1.
06/25/2008 ROBERT SHERRY WATER REVIEW Approved
06/25/2008 DAVE MANN FIRE REVIEW Approved
06/25/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
06/25/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/25/2008 JASON GREEN ENGINEERING REVIEW Approved
06/26/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1)

2) PROVIDE DETAILS FOR NEW WALLS AND INFILL CONSTRUCTION.

3) PROVIDE CLEAR FLOOR SPACE AND PULL SIDE CLEARANCES AT DOOR LEADING TO ACCESSIBLE RAMP ADJACENT TO VAULT. CLEAR SPACES TO BE PER ANSI 117.1 SECTION 404.

4) INDICATE ACCESSIBLE ROUTE FROM STREET AND ACCESSIBLE PARKING.

5) INDICATE ON PLANS THAT SITE IS 100% ACCESSIBLE (VERIFY ELEVATORS AND RESTROOMS0 OR DOCUMENT 20% CONSTRUCTION COST TOWARD ACCESSIBILITY PER IBC CHAPTER 34.
07/14/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed