Permit Number: T08CM02191
Parcel: 12706010A

Address:
40 N SWAN RD 02

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02191
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2008 TERRY STEVENS ZONING REVIEW Approved
06/20/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/20/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02191 6/20/08

1. Feeder to new Panel A, #4 with ampacity 85A, is not protected by the 100A CB in existing Panel E2.
2. HP-1, 26 FLA, would have 3120VA per phase, not 2284. With largest motor considered, this figure would be even larger.
06/20/2008 ROBERT SHERRY WATER REVIEW Approved
06/20/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/20/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
06/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/20/2008 JASON GREEN ENGINEERING REVIEW Approved
06/20/2008 MARTIN BROWN FIRE REVIEW Approved
06/20/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed