Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02191
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/20/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02191 6/20/08 1. Feeder to new Panel A, #4 with ampacity 85A, is not protected by the 100A CB in existing Panel E2. 2. HP-1, 26 FLA, would have 3120VA per phase, not 2284. With largest motor considered, this figure would be even larger. |
| 06/20/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/20/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/20/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 06/20/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/20/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/20/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/20/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |