Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
06/20/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02191 6/20/08 1. Feeder to new Panel A, #4 with ampacity 85A, is not protected by the 100A CB in existing Panel E2. 2. HP-1, 26 FLA, would have 3120VA per phase, not 2284. With largest motor considered, this figure would be even larger. |