Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02138
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02138 6/18/08 1. Fault calculation needs to be based on 2-3/0, not just one. PLS NOTE THE FOLLOWING: "c" value for 3/0, if installed in metallic conduit, is aprox. 12844, not 13923. TEP AFC is given at the secondary to the utility transformer. |
| 06/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |