Permit Number: T08CM02138
Parcel: 13001004B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02138
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
06/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/17/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02138 6/17/08

1. If EC-1 is rooftop-mounted, please specify GFCI receptacles.
2. New Panel A is rated for 22,000 AIC. Not eon One Line Diagram calls for a 22.10K series rating.
3. Show fault calculations for F2.
06/17/2008 ROBERT SHERRY WATER REVIEW Approved
06/17/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/17/2008 PAUL MACHADO ENGINEERING REVIEW Approved
06/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a detail for the water heater support.
06/17/2008 DAVE MANN FIRE REVIEW Approved No storage above 12'-0" AFF
06/17/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
06/18/2008 GERRY KOZIOL WWM REVIEW Approved