Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02138
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/17/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02138 6/17/08 1. If EC-1 is rooftop-mounted, please specify GFCI receptacles. 2. New Panel A is rated for 22,000 AIC. Not eon One Line Diagram calls for a 22.10K series rating. 3. Show fault calculations for F2. |
| 06/17/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/17/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/17/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a detail for the water heater support. |
| 06/17/2008 | DAVE MANN | FIRE | REVIEW | Approved | No storage above 12'-0" AFF |
| 06/17/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 06/18/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |