Permit Number: T08CM02121
Parcel: 124082420

Address:
55 N CHERRY AV 4

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM02121
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2008 JWILLIA5 BUILDING-COMMERCIAL REVIEW Approved
06/16/2008 STEVE SHIELDS ZONING REVIEW Approved
06/16/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/17/2008 DAVE MANN FIRE REVIEW Approved
06/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/20/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02121 6/17/08

1. Manufacturer instructions call for a 30A dryer branch circuit. Plans provide 20A circuit.
2. Manufacturer insturcts the contractor to fuse the 30A dryer circuit, which is not usual for a cord-connected appliance. Please clarify.
3. Clarify load requirements. If the dryer is 1500VA, then it would only draw 6.25A at 240V, and would not need a 30A circuit.
4. Provide electrical line diagram.
5. Provide service load calculations.
06/20/2008 ROBERT SHERRY WATER REVIEW Passed
06/20/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/24/2008 GERRY KOZIOL WWM REVIEW Approved
10/15/2008 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2008 DELMA ROBEY OUT TO CUSTOMER Completed