06/20/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02121 6/17/08

1. Manufacturer instructions call for a 30A dryer branch circuit. Plans provide 20A circuit.
2. Manufacturer insturcts the contractor to fuse the 30A dryer circuit, which is not usual for a cord-connected appliance. Please clarify.
3. Clarify load requirements. If the dryer is 1500VA, then it would only draw 6.25A at 240V, and would not need a 30A circuit.
4. Provide electrical line diagram.
5. Provide service load calculations.