Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM02121
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2008 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/16/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/16/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/17/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/20/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM02121 6/17/08 1. Manufacturer instructions call for a 30A dryer branch circuit. Plans provide 20A circuit. 2. Manufacturer insturcts the contractor to fuse the 30A dryer circuit, which is not usual for a cord-connected appliance. Please clarify. 3. Clarify load requirements. If the dryer is 1500VA, then it would only draw 6.25A at 240V, and would not need a 30A circuit. 4. Provide electrical line diagram. 5. Provide service load calculations. |
| 06/20/2008 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 06/20/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/24/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/15/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/15/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |