Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02056
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/13/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the common exhaust duct to provide a minimum velocity of 1500 FPM. 2. Show how the additional makeup air from the existing evaporative cooler is to be introduced into the room without affecting the comfort of the occupants. |
| 06/13/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide freeze protection for the water supply to the new MAU. 2. Show how the MAU will be drained. |
| 06/13/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/13/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/13/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 06/20/2008 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 06/20/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 06/20/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 06/24/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |