Permit Number: T08CM02056
Parcel: 126050280

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02056
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2008 DAVE MANN FIRE REVIEW Approved
06/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the common exhaust duct to provide a minimum velocity of 1500 FPM.
2. Show how the additional makeup air from the existing evaporative cooler is to be introduced into the room without affecting the comfort of the occupants.
06/13/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide freeze protection for the water supply to the new MAU.
2. Show how the MAU will be drained.
06/13/2008 ROBERT SHERRY WATER REVIEW Approved
06/13/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/13/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
06/20/2008 DROBEY1 ZONING REVIEW Needs Review
06/20/2008 DROBEY1 WWM REVIEW Needs Review
06/20/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/24/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2008 DELMA ROBEY OUT TO CUSTOMER Completed