Permit Number: T08CM02055
Parcel: 13316030G

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM02055
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2008 MARTIN BROWN FIRE REVIEW Approved
09/05/2008 ROBERT SHERRY WATER REVIEW Denied 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of the water meter. Reference: Section 103.2.3, UPC 2006.
2. Reduced pressure backflow prevention assemblies used to protect the public water supply are required to be installed in locations accessible to Tucson Water. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
09/09/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 22,119 Square Feet of Office; $107,216.56
09/09/2008 GERRY KOZIOL WWM REVIEW Denied UASA-TUCSON CANCER CENTER EXPANSION
CONNECTING TO ON-SITE PRIVATE SEWER PV99-002
NEED REVIEW OF CAPACITY OF EXSISTIN ON-SITE PRIVATE SEWER TO HANDLE INCREASED FLOW
09/10/2008 TERRY STEVENS ZONING REVIEW Denied 09/10/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/11/2008 VFLORES1 OUT TO CUSTOMER Completed
09/11/2008 SUE REEVES REJECT SHELF Completed