Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02046
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. MECHANICAL ENGINEER DID NOT CONFIRM ACCESSIBILITY OF THE SPECIFIED EYEWASH PER YOUR COMMENT #3. VERIFY. |
| 09/15/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/15/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Details 2/A2.1 and 3/A2.1 both show a "latchable access panel" that blocks what appears to be the leg space of the teacher's station. Clarify the proposed location of the emergency gas shut off valve to show that it is readily accessible. Reference: Section 1212.3 (D), UPC 2006. |
| 09/15/2008 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/03/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 10/03/2008 | SUE REEVES | REJECT SHELF | Completed |