Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM02044
Parcel: 11006134D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02044
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
06/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the dryer vent is to be routed.
06/12/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/12/2008 ROBERT SHERRY WATER REVIEW Approved
06/12/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEW EXAM ROOM SINK NEEDS TO BE 2'-10" A.F.F. AS PER ICC 117.1
2. TOILETS DO NOT MEET ICC 117.1 LAV ENCROACHMENT INTO TOILET CLEAR SPACE. AN APPEAL TO USE "ADA" TOILET COMPLIANCE IS ACCEPTABLE.
06/12/2008 BIANCA RAMIREZ ENGINEERING REVIEW Needs Review
06/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied If hot water is supplied to the lavatories, show how the water temperature is to be limited to a maximum of 110 degrees Fahrenheit.
06/12/2008 MARTIN BROWN FIRE REVIEW Approved
06/18/2008 CAGUILA1 WWM REVIEW Needs Review
06/18/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review