Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM02031
Parcel: 11105026F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02031
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/17/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/17/2008 GERRY KOZIOL WWM REVIEW Passed