Permit Number: T08CM02026
Parcel: 138200560

Address:
7042 S LUNDY DR

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM02026
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 9-26-08
Activity: T8CM02026
Address: 7042 S.Lundy Dr.
Applicant: Luciano Fragozo

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL PLANS:
2. Specify the method of uplift resistance between new bearing walls to existing roof structure (detail G).
3. Provide detail for new parapet construction where existing roof eaves will be removed.
4. Specify all hardware to be used.
5. Provide moment resisting hardware at wood post connection to concrete column.
6. Provide cross section detail for roof framing at dormers on either side of entry.
7. Specify the size and location of all roof scuppers.
8. Clarify ledger connections to walls.
9. Provide web-filler for I-Joists supported by face mount hangers.
10. Provide manufacturer and series of I-Joists.
11. Specify location of construction for detail D.
12. Specify sag-resistant gypsum when applied to framing members spaced 24" o.c.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2008 CPIERCE1 OUT TO CUSTOMER Completed