Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM02020
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T08CM02020, 295 W 4th st Electrical denied for the following: 1. Sheet E6.1 now shows 3 relay panels and a master switch, not previously in the other plans. Provide information on relay panels ( cut sheet ), provide a one line diagram on how actual wiring is to be made, lighting conductors wired from panels through relay panels, how relay panels powered, number of conductors in conduits and so forth. Ray T Majuta ,Elect Plan CK, City of Tucson, 5/17/10 Ray.Majuta@tucsonaz.gov 520-837-49878 |
| 06/03/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Two full sets of construction drawings were submitted. All the sheets that are not changed have already been approved and signed. For this revision, please submit revised sheets only for review, approval and signatures. |