Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02014
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/11/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/11/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
06/11/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/11/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. DETAIL 1 ON SHEET A2: TOP OF PARTITION WALL MUST BE BRACED TO MEET LATERAL LOAD REQUIREMENTS OF 2006 IBC. |
06/11/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/12/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/12/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the proposed water heater is to be supported from the building structure. Reference: Section 314.5, UPC 2006. 2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 3. Clarify the water heater detail 202; is a mixing valve being installed? 4. Clarify the proposed use of the three-compartment sink and show how it is to be drained. |
06/12/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/25/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
06/25/2008 | CPIERCE1 | WWM | REVIEW | Needs Review |