Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM02014
Parcel: 119046070

Address:
502 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02014
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
06/11/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
06/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/11/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. DETAIL 1 ON SHEET A2: TOP OF PARTITION WALL MUST BE BRACED TO MEET LATERAL LOAD REQUIREMENTS OF 2006 IBC.
06/11/2008 MARTIN BROWN FIRE REVIEW Approved
06/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the proposed water heater is to be supported from the building structure. Reference: Section 314.5, UPC 2006.
2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
3. Clarify the water heater detail 202; is a mixing valve being installed?
4. Clarify the proposed use of the three-compartment sink and show how it is to be drained.
06/12/2008 ROBERT SHERRY WATER REVIEW Approved
06/25/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/25/2008 CPIERCE1 WWM REVIEW Needs Review