Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02008
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 06/11/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02008 6/11/08 1. AFC of 22,000A as published by TEP pertains to underground, not overhead services. Add the following note to the plans: "Contractor shall provide Electrical Inspector with TEP available fault current before final electrical clearance." 2. Upon first review it was not stated that this is for a CONSTRUCTION trailer. Provide the Activity Number for the actual construction project. |
| 06/16/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review |