Permit Number: T08CM02008
Parcel: 103090350

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02008
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Passed
06/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02008 6/11/08

1. AFC of 22,000A as published by TEP pertains to underground, not overhead services. Add the following note to the plans: "Contractor shall provide Electrical Inspector with TEP available fault current before final electrical clearance."
2. Upon first review it was not stated that this is for a CONSTRUCTION trailer. Provide the Activity Number for the actual construction project.
06/16/2008 CPIERCE1 ZONING REVIEW Needs Review