Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02008 6/10/08

1. We were informed at the counter that this is to power a trailer. Indicate on the plans what is being powered.
2. Provide specification for the box being powered an connected to the bigger box.
3. Provide a disconnecting means per NEC 550.11 (A).
4. Provide TEP available fault current.
5. Provide fault current rating of equipment.
06/11/2008 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
06/11/2008 CAGUILA1 ZONING REVIEW Needs Review