Permit Number: T08CM01918
Parcel: 12417157B

Address:
1050 E 19TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01918
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2008 STEVE SHIELDS ZONING REVIEW Approved
06/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations
06/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01918 6/5/08

1. Circuit 6 is overloaded.
2. Circuit breaker appears too large for the heat pump. Please revisit name plate information and on-site overcurrent protection.
3. Please correct math for amperage calculations for panel. For example, total amps are 97, not 56, and phase a amps are 88.1, not 56.0.
06/05/2008 ROBERT SHERRY WATER REVIEW Approved
06/05/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/05/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
06/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/05/2008 PAUL MACHADO ENGINEERING REVIEW Approved
06/11/2008 DROBEY1 FIRE REVIEW Needs Review
06/11/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2008 DELMA ROBEY OUT TO CUSTOMER Completed