Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01918
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation calculations |
| 06/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01918 6/5/08 1. Circuit 6 is overloaded. 2. Circuit breaker appears too large for the heat pump. Please revisit name plate information and on-site overcurrent protection. 3. Please correct math for amperage calculations for panel. For example, total amps are 97, not 56, and phase a amps are 88.1, not 56.0. |
| 06/05/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/05/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/05/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures |
| 06/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/05/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/11/2008 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 06/11/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/11/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |