Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01845
Parcel: 138144510

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T08CM01845
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2008 STEVE SHIELDS ZONING REVIEW Approved
06/04/2008 STEVE SHIELDS ZONING_QA REVIEW Passed
06/04/2008 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
06/04/2008 PAUL MACHADO ENGINEERING_QA REVIEW Passed
06/04/2008 DAVE MANN FIRE REVIEW Approved
06/04/2008 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2008 DELMA ROBEY OUT TO CUSTOMER Completed