Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01844
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the fan coil unit is to be supported from the structure. 2. Revise the control of the exhaust fan to prevent recirculation of the air from the restroom. |
| 06/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/05/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/05/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/05/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a cleanout for the water closet. 2. Show how the hot water temperature is to be controlled at the lavatory. |
| 06/06/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 06/06/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 06/06/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |