Permit Number: T08CM01844
Parcel: 133146610

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01844
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2008 DAVE MANN FIRE REVIEW Approved
06/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the fan coil unit is to be supported from the structure.
2. Revise the control of the exhaust fan to prevent recirculation of the air from the restroom.
06/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/05/2008 ROBERT SHERRY WATER REVIEW Approved
06/05/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/05/2008 PAUL MACHADO ENGINEERING REVIEW Approved
06/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout for the water closet.
2. Show how the hot water temperature is to be controlled at the lavatory.
06/06/2008 CPIERCE1 WWM REVIEW Needs Review
06/06/2008 CPIERCE1 ZONING REVIEW Needs Review
06/06/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed