Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM01839
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/10/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/10/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
07/14/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/23/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The revised architectural plan (A1.1) shows a "point-of-use" water dispenser. Since the plumbing plans do not show the unit being connected to the water distribution piping, it is assumed that it is a bottled water dispenser. Provide an approved appeal to the building official for the use of a bottled water dispenser or provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy. 2. Water pipe sizing calculations do not appear on the revised plumbing drawings (xref?). Show how the water piping was sized. Reference: Sections 103.2.3 and 610.1, UPC 2006. |
07/23/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Show how the unit heater is to be attached to the building structure (i.e. how does the all-thread connect to the building structure and just what is the structure composed of?). Reference: Section 302.1, IMC 2006. 2. Provide the structural calculations to show that the Type I hood, with its exhaust fan and grease duct, is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. 3. Show how the hood installation detail (8/A6.1) is able to provide the clearance requirements of Sections 507.9 and 507.10, IMC 2006. 4. Comment not addressed. Provide information on the mechanical drawings to show that the operation of the Type I hood and the hood exhaust fan complies with Section 507.2.1.1, IMC 2006 |
07/28/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED 5TH FLOOR CREDIT EVALUATION |
08/04/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: August 4, 2008 SUBJECT: TI: Detail Passion for the Love of Pastry TO: Metro Permit Express LOCATION: 4500 E Speedway, T14S, R14E, Section 10, Ward 6 REVIEWERS: Bianca Ramirez, CFM ACTIVITY: T08CM01839 (First Review) RESUBMITTAL REQUIRED: Building Plan SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed building plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal. Please include a response letter to the comments along with the corrected copoes of the building plan. Building Plan: Floodplain Use Permit Required. 1. Cost estimate for material and labor needs to be submitted 2. Either appraisal or assessor property evaluation needs to be provided for the value of the structure. 3. Further review will be required once appropriate documentation has been provided. 4. Additional Comments may be forthcoming. If you have any questions please feel free to contact me at 520-837-4928 or bianca.ramirez@tucsonaz.gov. Thank you, Bianca C. Ramirez, CFM Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4928 office (520) 879-8010 fax |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/06/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
08/06/2008 | SUE REEVES | REJECT SHELF | Completed |