Permit Number: T08CM01839
Parcel: 12601003C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01839
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
06/04/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01839 6/4/08

1. R2 would draw almost 28A. The 15A CB would not allow it to start.
2. Phases B and C are overloaded at 109A and 104A, respectively. Please note that the demand factor, NEC Table 220.56 allows, would be 0.90 for 3 pieces of equipment on Phase A, 0.70 for 5 pieces of equipment on Phase B, and 0.80 for 4 pieces of equipment on Phase C.
3. Please provide fault calculations for new panel.
06/04/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. LOCATE VERTICAL GRAB BAR IN RESTROOM PER ICC/ANSI A117.1-2003.
2. LOCATE PAPER DISPENSER IN RESTROOM PER ICC/ANSI A117.1-2003.
3. HIGH/LOW DRINKING FOUNTAIN LOCATION? CAN ALTERNATELY USE SINGLE POINT-OF-USE WATER DISPENSER OR PROVIDE OVER-THE COUNTER WATER.
06/05/2008 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/05/2008 DROBEY1 PLUMBING-COMMERCIAL REVIEW Needs Review
06/05/2008 DROBEY1 WATER REVIEW Needs Review
06/05/2008 DAVE MANN FIRE REVIEW Denied Code review says building is un-sprinklered and sprinklered. Type of hood is unclear I or II?
06/05/2008 DROBEY1 WWM REVIEW Needs Review
06/05/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/05/2008 DROBEY1 ENGINEERING REVIEW Needs Review