Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01839
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/03/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/04/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01839 6/4/08 1. R2 would draw almost 28A. The 15A CB would not allow it to start. 2. Phases B and C are overloaded at 109A and 104A, respectively. Please note that the demand factor, NEC Table 220.56 allows, would be 0.90 for 3 pieces of equipment on Phase A, 0.70 for 5 pieces of equipment on Phase B, and 0.80 for 4 pieces of equipment on Phase C. 3. Please provide fault calculations for new panel. |
06/04/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. LOCATE VERTICAL GRAB BAR IN RESTROOM PER ICC/ANSI A117.1-2003. 2. LOCATE PAPER DISPENSER IN RESTROOM PER ICC/ANSI A117.1-2003. 3. HIGH/LOW DRINKING FOUNTAIN LOCATION? CAN ALTERNATELY USE SINGLE POINT-OF-USE WATER DISPENSER OR PROVIDE OVER-THE COUNTER WATER. |
06/05/2008 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
06/05/2008 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
06/05/2008 | DROBEY1 | WATER | REVIEW | Needs Review | |
06/05/2008 | DAVE MANN | FIRE | REVIEW | Denied | Code review says building is un-sprinklered and sprinklered. Type of hood is unclear I or II? |
06/05/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
06/05/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
06/05/2008 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |