Permit Number: T08CM01783
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01783
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/04/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 1D-3; PARTITION PLAN: RESTROOM IS NOT ADA COMPLIANT (IS NOT REQUIRED TO BE COMPLIANT). REMOVE ANY SIGNAGE INDICATING ADA COMPLIANCE.
2. SHEET 1D-3; PARTITION PLAN: PER 2006 IBC, SECTION 2902.4, ACCESS TO A RESTROOM MAY NOT PASS THROUGH A STOCK ROOM. MOVE 'STOCK ROOM' NOTATION TO AREA BELOW THE RESTROOM, AND RENAME THE AREA IN FRONT OF THE RESTROOM TO 'CORRIDOR'.
3. SHEET 1D-3; PARTITION LEGEND; WALL TYPES 3, 4, 5, 6, AND 7: DETAIL DIAGONAL BRACING AT THE TOP OF THE PARTITIONS, INDICATING BRACING SIZE, LOCATION, AND CONNECTION TO THE TOP OF THE PARTITION AND TO THE ROOF.
4. 1/8" MINIMUM LETTERING SIZE REQUIRED.
06/12/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/24/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Second request. Revise the font to a minimum of 1/8", all upper case.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2008 CPIERCE1 OUT TO CUSTOMER Completed
07/10/2008 SUE REEVES REJECT SHELF Completed