Permit Number: T08CM01781
Parcel: 137055300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01781
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2008 DAVE MANN FIRE REVIEW Denied A second exit is required. It cannot go thru lens manufacturing area. See IFC 1014.2.
06/03/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Impact Fee's will be charged if permit is not issued on or before 8/23/07.
06/04/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. SHELL DRAWINGS FOR MALL REQUIRED.
2. EXIT CAN NOT PASS THROUGH A ROOM THAT CAN BE LOCKED PER 2006 IBC SECTION 1014.2.1, 2.2 AND 2.3.
3. REFERENCE CODES ARE 2006 IBC AND ICC/ANSI A117.1-2003 FOR ACCESSIBILITY. CHANGE ALL "ADA" REFERENCES TO THESE CODES.
4. TOILET DOES NOT COMPLY WITH ICC 117.1, SECTION 604.3.2. REDESIGN TOILET ROOM TO 2006 IBC/ICC 117.1 STANDARDS . PROVIDE ENLARGED RESTROOM PLAN WITH DIMENSIONS AND CLEARANCES REQUIRED. PROVIDE ALL REQUIRED TOILET ELEVATIONS (DETAILS 1, 2, 3 AND 4 A-4) TO MEET ICC 117.1, CHAPTER 6.
5. BRACE TOP OF NEW INTERIOR WALLS TO RESIST LOADS PER 2006 IBC 1607.13. REVISE DETAIL 16/A-3 ACCORDINGLY.
6. 1/8" LETTERING REQUIRED ON ALL DRAWINGS. WRITTEN APPEAL MAY BE MADE TO THE BUILDING OFFICIAL, JESSIE SANDERS.
7. AT SHEET A-5, RE-REVIEW ALL ACCESSIBILITY DETAILS AND DIMENSIONS TO COMPLY WITH 2006 IBC/ICC 117.1 NOT "ADA".
8. PROVIDE STRUCTURAL MOUNTING DETAILS AND CALCULATIONS FOR ALL NEWLY ROOF MOUNTED EQUIPMENT.
9. PROVIDE STRUCTURAL MOUNTING DETAILS AND CALCULATIONS FOR ALL EXHAUST FANS SUPPORTED FROM THE BOTTOM OF THE EXITING STEEL JOISTS.
10. PROVIDE STRUCTURAL MOUNTING DETAILS AND CALCULATIONS FOR WALL MOUNTED WATER HEATER.
06/06/2008 VFLORES1 WWM REVIEW Needs Review
06/06/2008 VFLORES1 PLUMBING-COMMERCIAL REVIEW Denied .
06/06/2008 VFLORES1 MECHANICAL-COMMERCIAL REVIEW Denied
06/10/2008 THAUSER1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2008 THAUSER1 OUT TO CUSTOMER Completed