Permit Number: T08CM01781
Parcel: 137055300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01781
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
06/02/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
3. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
4. Show how the submitted calculations provide adequate ventilation comparable to that required by Section 403.3, IMC 2006.
5. Clarify the key notes for the exhaust fans. Show how the restroom exhaust complies with Section 403.2.1 (3), IMC 2006.
06/02/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/02/2008 ROBERT SHERRY WATER REVIEW Approved
06/02/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHELL DRAWINGS FOR MALL REQUIRED.
2. EXIT CAN NOT PASS THROUGH A ROOM THAT CAN BE LOCKED PER 2006 IBC SECTION 1014.
3. REFERENCE CODES ARE 2006 IBC AND ICC/ANSI A117.1-2003.
4. ENLARGE RESTROOM PLAN WITH DIMENSIONS/CLEARANCES PER ANSI. RESTROOM ELEVATIONS TO MEET ANSI CHAPTER 6.
5. BRACE TOP OF NEW INTERIOR WALLS TO RESIST LOADS PER 2006 IBC 1607.13.
6. 1/8" LETTERING REQUIRED ON ALL DRAWINGS. WRITTEN APPEAL MAY BE MADE TO THE BUILDING OFFICIAL, JESSIE SANDERS.
06/02/2008 CPIERCE1 WWM REVIEW Needs Review
06/02/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
3. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
6. Provide a vent for the solids interceptor. Reference: Section 1009.4, UPC 2006.
06/02/2008 JASON GREEN ENGINEERING REVIEW Approved
06/02/2008 DAVE MANN FIRE REVIEW Denied A second exit is required. It cannot go thru lens manufacturing area.
06/02/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review