Permit Number: T08CM01759
Parcel: 12513002C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM01759
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/30/2008 TERRY STEVENS ZONING REVIEW Approved
05/30/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
05/30/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01759 5/30/08

1. NEMA 1 enclosure is not suitable for installation outdoors. Bill of Materials Itsm #64.
2. Could not find Item #65, Safety Switch, on plans.
3. Minimum font size 1/8". Please enlarge plans.
4. Provide panel and circuit number for sign circuits.
5. Provide panel schedule and panel load calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2008 CINDY AGUILAR OUT TO CUSTOMER Completed