Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM01759
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/30/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 05/30/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 05/30/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01759 5/30/08 1. NEMA 1 enclosure is not suitable for installation outdoors. Bill of Materials Itsm #64. 2. Could not find Item #65, Safety Switch, on plans. 3. Minimum font size 1/8". Please enlarge plans. 4. Provide panel and circuit number for sign circuits. 5. Provide panel schedule and panel load calculations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/11/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |