Permit Number: T08CM01747
Parcel: 14119516A

Address:
9900 E RITA RD

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM01747
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01747 6/3/08

1. Fixture A does not appear to be full cutoff, from the photograph. Provide photometrics demonstrating full cutoff characteristic from manufacturer.
2. Provide a fixture which, when mounted at the angle indicated in the drawing, will be full cutoff.
3. The 50W HPS fixture appears to have too low of a lumen count. Provide manufacturer documentation of mean lumens.
4. It is not clear from the drawings and cutsheet that the flood lights are full cutoff in their mounting orientation.
5. Cut sheet for flood light does not include lighting source, wattage, or mean lumens. Not possible to complete review for Lighting Code compliance.
6. Provide a description of existing lighting, including quantity, source type, and wattages.