Permit Number: T08CM01747
Parcel: 14119516A

Address:
9900 E RITA RD

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM01747
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2008 HEATHER THRALL ZONING REVIEW Approved
05/29/2008 PAUL MACHADO ENGINEERING REVIEW Approved
05/30/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/30/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01747 5/30/08

1. Provide location of the existing panel on the plans.
2. Put the job address on all sheets.
3. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
4. Provide cut sheets for lighting fixtures.
5. Equipment Grounding Conductor shall be #10, not #12. Reference NEC Table 250.122.
6. Provide load calculations for the entire panel, not just additional load.
05/30/2008 DAVE MANN FIRE REVIEW Approved
06/03/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2008 VFLORES1 OUT TO CUSTOMER Completed