Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01703
Parcel: 13409019L

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01703
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2008 DAVE MANN FIRE REVIEW Approved
05/27/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/28/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/28/2008 ROBERT SHERRY WATER REVIEW Approved
05/28/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
05/28/2008 JASON GREEN ENGINEERING REVIEW Approved
05/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/28/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/29/2008 GERRY KOZIOL WWM REVIEW Approved