Review Details: COMMERCIAL TI

Permit Number - T08CM01683
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
05/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the operating weights of the AC unit and the condensing unit.
2. Show that the installation of the mechanical units will not harm the structure.
3. Provide an auxiliary drain pan or a secondary drain for the AC unit per Section 307.2.3, IMC 2006.
4. Clearly show the location of the condensing unit.
05/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. An indirect waste receptor shall not be located inside of a cabinet.
2. Revise the font size on the drawing to a minimum of 1/8".
05/23/2008 ROBERT SHERRY WATER REVIEW Approved
05/23/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED STRUCTURAL CALCULATIONS FOR HVAC UNIT SUPPORT FROM BOTTOM OF EXISTIN STRUCTURE
2. NEED EXPERATION DATE ON SEAL.
05/23/2008 PAUL MACHADO ENGINEERING REVIEW Approved
05/23/2008 MARTIN BROWN FIRE REVIEW Approved
06/13/2008 CPIERCE1 WWM REVIEW Needs Review
06/13/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01683 6/13/08

1. Show that existing Panel B-5 is not overloaded.
2. Provide TEP available fault current and fault calculations for New Panel TA.