Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01683
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/23/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
05/23/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the operating weights of the AC unit and the condensing unit. 2. Show that the installation of the mechanical units will not harm the structure. 3. Provide an auxiliary drain pan or a secondary drain for the AC unit per Section 307.2.3, IMC 2006. 4. Clearly show the location of the condensing unit. |
05/23/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. An indirect waste receptor shall not be located inside of a cabinet. 2. Revise the font size on the drawing to a minimum of 1/8". |
05/23/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/23/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED STRUCTURAL CALCULATIONS FOR HVAC UNIT SUPPORT FROM BOTTOM OF EXISTIN STRUCTURE 2. NEED EXPERATION DATE ON SEAL. |
05/23/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
05/23/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/13/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
06/13/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01683 6/13/08 1. Show that existing Panel B-5 is not overloaded. 2. Provide TEP available fault current and fault calculations for New Panel TA. |
06/13/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |