Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM01629
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/12/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | DO NOT ACCESS TOILET THROUGH WORK ROOM. |
06/12/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/12/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not adequately addressed. Show that the make up air unit is adequately supported on the roof. (i.e. provide structural calculations and details) "Sales Presentation" drawings that do not show the location of the make up air unit are not suitable to show that the unit is adequately supported. |