Permit Number: T08CM01629
Parcel: 114600830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01629
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2008 DAVE MANN FIRE REVIEW Approved
05/30/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/30/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED EXIT CORRIDOR, REFERENCE 2006 IBC, SECTION 1014.2 (2.4)
2. PROVIDE STRUCTURAL MOUNTING DETAIL FOR NEW HVAC ROOF MOUNTED UNIT PLUS STRUCTURAL CALCULATIONS.
05/30/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Show that the make up air unit is adequately supported on the roof. (i.e. provide structural calculations and details)
06/12/2008 CPIERCE1 WWM REVIEW Needs Review
06/12/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed