Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01628
Parcel: 13615378B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01628
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The specified grease duct insulation (Fyrewrap EZ 1.5) does not comply with the requirements of Section 506.3.10 (exception 1), IMC 2006; specifically, it has not been tested per Section 16.4, ASTM E 2336-04.
2. Clarify the amount of outside air being provided by the makeup air unit, Evap-1. The plans indicate 5180 CFM but the equipment list shows 6081 CFM. Section 508.1, IMC 2006 requires that the supplied makeup air be approximately equal to the exhaust air but with only 5180 CFM, the suite is 1161 CFM short of outside air.
3. Verify with the manufacturer's representative the ability of AC-1 to function properly with the amount of outside air that you have scheduled (1,350 CFM OSA, 2,000 CFM total air circulation)
08/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout located downstream of the hydromechanical grease interceptor to comply with the requirements of Section 707.4, UPC 2006.
2. Provide the listing information for the specified hydromechanical grease interceptor; the specified model (Watts G4020) is not shown on the manufacturer's web site.
3. The gas table has not been changed since the last submittal. The energy content of the natural gas in this area is approximately 1000 BTU per cubic foot. Resize the piping per Section 1209.4.3, UPC 2006. Reference: Section 1209.1, UPC 2006.