Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM01627
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED WASTEWATER 8TH FLOOR REVIEW OF ADJACENT PROPERTY CONNECTIONG TO SEWER WITH A UTILITY EASEMENT |
| 06/13/2008 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T08CM01627 6/20/08 917 S. ARIZONA AVE. #1 & #2 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. 4. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF THE STATE BOARD OF TECHNICAL REGISTRATION. SITE PLAN: 1. PLEASE PROVIDE TWO WATER METERS. ONE FOR EACH UNIT. IRC P2602.1.1 AS AMMENDED FLOOR PLANS: 1. PLEASE DIMENSION THE WIDTH OF THE STAIRWAY AND THE LANDING. 2. PLEASE PROVIDE FOR THE INCLUSIVE HOME DESIGN. i.e. DOOR HARDWARE, HEIGHT OF RECEPTACLES, etc. 3. THE FIREWALL SHOULD EXTEND THROUGH THE PORCHES. STRUCTURAL PLANS: 1. THE 4X8 PORCH BEAM APPEARS TO BE INADEQUATE TO SUPPORT THE A/C UNIT. WHAT IS THE WEIGHT OF THE INTENDED UNIT? I USED 400# ON THE BEAM. I DIDN'T KNOW WHERE ON THE RAFTER SPAN THE LOAD WOULD BE LOCATED. PLEASE JUSTIFY THE 4X8. 2. PROVIDE DETAILS FOR TWO STORY WALL BRACING. R602.10.6.1 ITEM 2 SECTIONS - DETAILS - MISC. NOTES: 1. 1 / A-4 ; DESCRIBE THE ½" SHEATING ON THE EXTERIOR SIDE OF THE STUDS. 2. STRUCTURAL NOTES / A-4 ; PLEASE CHANGE REFERENCES TO THE 2003 IRC TO THE 2006 IRC. 3. 1 / A-5 ; PLEASE SPECIFY THE CONCRETE ANCHORS. 4. FRAMING PLAN / A-5 ; SPECIFY L1 AND L2. 5. 1 / A-5 ; PROVIDE THE FIREBLOCK @ THE CEILING LINE. 6. WINDOW SCHEDULE / A-2 ; INDICATE THE OPENING PORTION OF THE WINDOWS. 7. PROVIDE BRACED WALL PANEL DETAILS FOR THE TWO STORY. 8. 7, 8 / A-6 ; PLEASE SPECIFY THE CEILING JOISTS AND SPACEING. 9. 8 / A-6 ; LU 26 IS ONLY 1 ½" WIDE AND WON'T FIT A 3X6. 5 / A-6 CALLS FOR 2X6. PLEASE RESOLVE 2X6 VS 3X6. 10. 2 / A-6 ; HOW LONG IS THE 2X6? HOW MANY PAIRS OF 16d? 11. 6 / A-6 ; MSTC 40 IS 3" WIDE. WILL ADEQUATE NAILING BE PROVIDED AT THE 1 I/2" WIDE STUDS? 12. 11 / A-6 ; THE R-15 DIFFERS FROM THE LISTED R-19 IN "R-VALUES AND U-FACTORS" / A-1. PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. 2.. WATER DISTRIBUTION / P-1 ; DUPLEXES REQUIRE TWO WATER METERS. P2902.1.1 , AMENDED 3. WATER DISTRIBUTION / P-1 ; THE WATER DEPARTMENT, 791-5945, LISTS THIS ADDRESS AS HAVING 36-43 PSI WATER PRESSURE. SECTION P2903.3 REQUIRES A MINIMUM OF 40 PSI AT THE BUILDING ENTRANCE. BOOSTER PUMPS ? 4. DWV DIAGRAM / P-1 ; PLEASE RAISE THE CLOTHES WASHER TRAP ABOVE THE HORIZONTAL DRAIN. ELECTRICAL PLANS: 1. FIRST FLOOR ELEC. / E-1 ; PROVIDE A RECEPTACLE WITHIN 6' OF THE ENTRY DOOR, TO THE LEFT. E3801.2.1 2. SECOND FLOOR / E-1 ; PLEASE PROVIDE A RECEPTACLE WITHIN 6' OF THE BEDROOM DOOR, NEXT TO THE FIRE WALL. E3801.2.1 AND E3801.2.2 ITEM 1 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/23/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/23/2008 | SUE REEVES | REJECT SHELF | Completed |