Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM01623
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM01623 8/19/08 1. Account for display receptacle on Ckt B-4 on panel schedule. 2. It appears that Phase A of Panel A has 109A when considering largest motor and continuous load, thus overloading the panel. Phase B not checked. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |