Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM01585
Parcel: 13623007R

Address:
2750 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM01585
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/16/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01585 5/16/08

1. Show panel and circuit number for all lights.
2. Show location of electrical panel on plans.
3. Provide panel schedule and load calculations.
4. Indicate total count of T8 flourescent bulbs.
5. Provide disconnecting means. NEC 600.6.
6. Demonstrate compliance with the Tucson Lighting code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
05/16/2008 MARTIN BROWN FIRE REVIEW Approved
06/10/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
06/10/2008 DROBEY1 ENGINEERING REVIEW Needs Review
06/10/2008 DROBEY1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2008 DELMA ROBEY APPROVAL SHELF Completed