Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM01581
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/16/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM01581 5/16/08 1. Show panel and circuit number for all lights. 2. Show location of electrical panel on plans. 3. Provide panel schedule and load calculations. 4. Indicate total count of T8 flourescent bulbs. 5. Provide disconnecting means. NEC 600.6. 6. Demonstrate compliance with the Tucson Lighting code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. |
| 05/16/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/10/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/10/2008 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 06/10/2008 | DROBEY1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/10/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 06/10/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 06/10/2008 | DELMA ROBEY | REJECT SHELF | Completed |