Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM01568
Parcel: 125040690

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM01568
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2008 GERRY KOZIOL WWM REVIEW Denied NEED TO REVIEW LOCATION OF CONNECTION TO PUBLIC SEWER
06/10/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM01568

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Show the water pipe size between the meter and point of connection for new plumbing, 2006 UPC 610.1.

FOUNDATION PLANS:

1. Note that grade away from foundations shall fall min 6" within the first 10', R401.3.

PLUMBING PLANS:

1. Provide a fixture unit schedule (to include existing dwelling fixtures) for determining required service pipe size serving both dwellings, UPC Tables 6-5 & 7-3.

MECHANICAL PLANS:

1. Remove the reference to the 1994 UMC on Mechanical note #1. This code is not recognized by the City of Tucson. http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html
2. Show a means of make-up air at the laundry closet, M1307.
3. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Specify recessed lighting with 3" separation from combustibles or IC listing, R808, and compliance with energy efficiency leakage, N1102.4.3.
2. Show a receptacle outlet within 3' of each lavatory basin in each bathroom, E3801.6.
3. Bathroom receptacles shall be on a separate 20 AMP circuit with no outlets at other locations, E3603.4. Change the circuit number at the hall smoke detector and light.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2008 DELMA ROBEY APPROVAL SHELF Completed
06/11/2008 DELMA ROBEY OUT TO CUSTOMER Completed
06/11/2008 GERARDO BONILLA REJECT SHELF Completed