Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01563
Parcel: 12904157A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM01563
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/09/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. This activity number has attached to it a petition of appeal from the building official allowing the use of the 2006 IPC. The code schedule at the front of the plan states that the 2006 UPC is to be used. Clarify which code is to be used.
2. The building numbers noted on the plan do not match up with the way the buildings are numbered in the field. Match the plan numbers with the on site building numbers.
3. See detail 2 on sheet P1.2. Reference: 909.1 and 909.1.1 2006 IPC. Wet venting is limited to any combination of fixtures within two bathroom groups located on the same floor. By this definition, a kitchen sink is not included in fixtures which may be wet vented.
4. The revised scupper detail (2/A4.2) now indicates an overflow weir that is only 3 in opening height; the minimum opening height is 4 per Section 1107.3, IPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2009 CPIERCE1 OUT TO CUSTOMER Completed