Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T08CM01563
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 2121 E BROADWAY T08CM01561, T08CM01562, T08CM01563, T08CM01564, T08CM01565, T08CM01566 Building Plan (1st Review) TRANSMITTAL DATE: September 23, 2008 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08cm01561.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 09/23/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide individual metering for the water supply to all new dwelling units. The metering may be private or utility installed. Reference: Section 301.4.1, IPC 2006, as amended by the City of Tucson. 2. Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project with a demand of 96 GPM. |
| 09/23/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/25/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:Casitas on East Broadway - 643 FU's @ SFR rate & 40FU's @ commercial rate for laundrys 2: Need to permit on-site private sewer- need DEQ review & approval if over 3000 gal/day - need copy of on-site private sewer for base map update 3: need manhole construction permit- PCDRWRD/3RD FL- Roy Montoya (740-6534) 4: need PCRWD review of road abandonment & retension of public sewer. |
| 09/25/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 09/30/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/04/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 02/04/2009 | SUE REEVES | REJECT SHELF | Completed |