Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM01561
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/08/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/15/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The addressing shown on the plans (Buildings 1A, 1B, 2A, 2B, etc) does not correspond to the recorded addresses (Buildings 1, 2, 3, 4, etc.). Revise the plans as required match the records or see Addressing in Pima County to resolve the situation. 2. Provide independent ventilation or an independent air conditioning system for the elevator machine room. Reference: Section 3006.2, IBC 2006. |
10/15/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The addressing shown on the plans (Buildings 1A, 1B, 2A, 2B, etc) does not correspond to the recorded addresses (Buildings 1, 2, 3, 4, etc.). Revise the plans as required match the records or see Addressing in Pima County to resolve the situation. 2. Revise the riser diagram 3/P1.1 to comply with the requirements of Table 910.4, IPC 2006. 3. Provide a cleanout at the base of each drainage stack per Section 708.3.4, IPC 2006. |
10/21/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/04/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
11/04/2009 | CPIERCE1 | REJECT SHELF | Completed |