Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01561
Parcel: 12904157A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM01561
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 2121 E BROADWAY
T08CM01561, T08CM01562, T08CM01563, T08CM01564, T08CM01565, T08CM01566
Building Plan (1st Review)

TRANSMITTAL DATE: September 23, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm01561.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
09/23/2008 ROBERT SHERRY WATER REVIEW Denied Provide individual metering for the water supply to all new dwelling units. The metering may be private or utility installed. Reference: Section 301.4.1, IPC 2006, as amended by the City of Tucson.
09/23/2008 MARTIN BROWN FIRE REVIEW Approved
09/25/2008 GERRY KOZIOL WWM REVIEW Denied 1:Casitas on East Broadway - 643 FU's @ SFR rate & 40FU's @ commercial rate for laundrys
2: Need to permit on-site private sewer- need DEQ review & approval if over 3000 gal/day - need copy of on-site private sewer for base map update
3: need manhole construction permit- PCDRWRD/3RD FL- Roy Montoya (740-6534)
4: need PCRWD review of road abandonment & retension of public sewer.
09/25/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
09/26/2008 RBROWN1 ADA REVIEW Passed As per research completed by Jessie Sanders, unless required otherwise by HUD, project is to be a 2006 IBC-ICC/ANSI 117.1 accessible compliance review which has been completed by 3rd Party, Wildan.
09/30/2008 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
02/04/2009 SUE REEVES REJECT SHELF Completed