Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01553
Parcel: 14044018C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01553
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2008 DAVE MANN FIRE REVIEW Denied For Buildings A and C

Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards. THE FACT THAT 1500 GPM MUST BE ADDED AS A HOSE ALLOWANCE.
4. The density required of the water supply.
11/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE BUILDING COMMENTS FOR T08CM01551.
11/24/2008 TERRY STEVENS ZONING REVIEW Approved
11/26/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/26/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide level service platforms and guards for the A/C units located on roofs with slopes of 3:12 or greater. Reference: Section 306.5.1, IMC 2006.
12/03/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved